Design guide · HMI & SCADA
HMI and SCADA design: modern screens you understand at a glance
A good screen is not the one that shows the most, but the one that lets you see what is going wrong first. This guide distills ISA-101, alarm management and UI/UX design, and brings them down to WinCC Unified and WinCC V8 with real resources you can download today.
- Eleven short chapters with figures you can touch
- Sourced figures: HSE, ISA, ASM Consortium, W3C
- A checklist for your next screen
HMIx team15 min readReviewed
Eleven minutes, 275 alarms
Why screen design is a matter of safety and money
On July 24, 1994, an explosion at the Texaco refinery in Milford Haven, Wales, injured 26 people and caused around £48 million in damage. The investigation by the UK regulator, the HSE, identified three key factors, and two of them were in the control room: there were too many alarms and they were poorly prioritized, and the displays did not help the operators understand what was happening HSE.
The number that sums up that day: in the last 11 minutes before the explosion, two operators had to recognize, acknowledge and act on 275 alarms. One every 2.4 seconds.
Eleven minutes, minute by minute
Target in normal operation
1 alarm every 10 min
Ceiling after a major upset
10 in the first 10 min
Milford Haven, 1994
275 in 11 min
Nobody can read, understand and decide at that pace. Two people's attention did not fail: an interface that treated the urgent and the irrelevant alike did.
The opposite effect has been measured too. In 2005, NOVA Chemicals and the ASM (Abnormal Situation Management) Consortium compared two groups of operators on simulators, facing the same upset scenarios: one group worked with traditional displays and the other with displays designed on human-factors principles ASM.
What changes when the screen changes
- Traditional interface
- Redesigned interface
- Upsets detected early
- Traditional interface: 10%
- Redesigned interface: 47.7%
- Scenarios solved successfully
- Traditional interface: 70%
- Redesigned interface: 95.5%
- Mean time to solve the upset
- Traditional interface: 18.1 min
- Redesigned interface: 10.6 min
Nearly five times more upsets caught early, and seven and a half minutes saved on each one. Without touching the process: only the screen.
ISA-101 without the jargon: what it asks for and what it doesn't
The reference standard for HMI design, explained in three minutes
ANSI/ISA-101.01-2015, “Human Machine Interfaces for Process Automation Systems,” is the reference standard for designing and maintaining HMIs in continuous, batch and discrete processes ISA. Its contribution is not a palette: it is a method.
In fact, ISA-101 does not tell you which color or which shape to use Control Global. It asks for something harder: that those decisions are made once, written down and followed on every screen. To get there it defines a lifecycle and three system documents.
The HMI lifecycle according to ISA-101
System standards
- 1
Philosophy
What the HMI is for and who it serves. The principles that are not up for negotiation.
- 2
Style guide
How it looks and behaves: colors, type, symbols, navigation.
- 3
Toolkit
The library of objects every screen is built from.
- Design
- Implement
- Operate
Continuous improvement
The third one, the toolkit, is where a project is won or lost. If every screen is drawn by hand, consistency does not survive the third one. If everything comes from a library of reusable symbols and controls, the style guide enforces itself and every improvement reaches the whole plant at once.
That is exactly what a dynamic SVG and a Custom Web Control are in WinCC: toolkit parts. Which is why the free HMIx catalog is a good place to start building yours.
The five-second test
Four display levels, each with a single question to answer
Look at a screen for five seconds, then look away. Do you know whether the plant is running well? That number is not from the standard; it is a classic usability test, and almost no screen traced from the P&ID passes it: a P&ID explains how the plant is built, not how it is behaving.
ISA-101 solves this with a four-level hierarchy Control Global. Each level answers a different question, and mixing two questions on one screen is the fastest way to answer neither.
One question per level
Level 1 · Overview
Is everything OK?
The operator's entire span of responsibility on a single screen. It is for situational awareness, not for operating: key indicators, trends and alarms, with no equipment detail.
What fits here: KPI dashboards, energy flows or status radars built as Custom Web Controls.
The hierarchy is collapsible: a small machine can live with two levels. What never changes is the direction, from the general to the particular. If you need parts for your Level 1, start with the KPI cards.
Color is a scarce resource
If everything calls for attention, nothing does
On the traditional screen at the top, red means four things at once: stopped pump, hot pipe, stop button and alarm. When one color says everything, it says nothing.
Bill Hollifield, co-author of The High Performance HMI Handbook, sums it up in a one-line rule: alarm colors are never used for anything else Control Global. The rest of the screen works in neutral tones, with equipment and piping in low contrast, so that the abnormal is literally the only thing in color.
There is a second reason, and it is physiological. About 1 in 12 men has some form of color vision deficiency, and the most common type makes it hard to tell red from green NEI: the very pair half the industry uses for running and stopped. See for yourself.
Six machines, two ways of telling the story
How many machines are in alarm?
Color only
Color + shape + text
The fix is called redundant coding: every state is told apart by at least two cues, such as shape and color, or brightness and a word. It is the same idea WCAG requires of any website in success criterion 1.4.1: color must never be the only means of conveying information W3C.
Two more numbers worth borrowing from web accessibility: a minimum contrast of 4.5:1 for text and 3:1 for the graphical elements people need to tell apart W3C. Mid gray on dark gray can be elegant and, at the same time, unreadable from six feet away.
A number is not information
The operator doesn't need the value: they need to know whether it is good
187.9 °C. Is that a lot? To know, you have to remember the normal range for that point, and repeat the effort for the hundreds of values in a plant. A bare number is data; it becomes information when its context travels with it.
The most effective way to provide it is an analog indicator: a scale with the normal range marked and a pointer. People recognize patterns far faster than they read digits Control Global: twenty aligned indicators are checked in a single glance, because the one out of line jumps out by itself.
The same value, with and without context
Data only
156.0°C
Is it good or bad?
With context
Normal
156.0°C
Normal range
Last few minutes
The other thing missing from traditional screens is time. Almost every display has one or two values that would be far easier to understand as a trend, and that trend has to be embedded in the graphic, not hidden in another window Control Global. A good trend answers one question: where am I compared with where I should be?
One detail that gives away a well-crafted screen: decimals. 62.4372% is no more precise than 62%; it just takes longer to read. To pick your parts, we have compared the best gauges and trend charts in the catalog.
Alarms: few, prioritized and with a response
ISA-18.2 and EEMUA 191, in the numbers people actually use
An alarm is not a notice or a status: it is a situation that requires the operator to do something, in time. The HSE puts it bluntly: process status indicators should not be designated as alarms HSE. Every alarm without a defined response is noise that hides the others.
The alarm management standards (ISA-18.2, EEMUA 191 and IEC 62682) agree on the orders of magnitude Chemical Engineering.
How many alarms per hour can one person handle?
6alarms/h
Target in normal operation
One every 10 minutes on average
12alarms/h
Maximum manageable in the long run
EEMUA 191, ISA-18.2 and IEC 62682
60alarms/h
The flood begins
More than 10 new alarms in 10 minutes
1,500alarms/h
Milford Haven, 1994
275 alarms in 11 minutes
Priority is the other half. About three priorities are enough, assigned by the severity of what happens if nobody responds, and distributed roughly like this HSE:
Recommended priority distribution
- 80%Low
- 15%Medium
- 5%High
For screen design this turns into three decisions. The alarm is drawn next to the affected equipment, not only in a list. Each priority has a shape, a color and a number that are not repeated on any other element. And the alarm summary is always visible, at every level; if the native list falls short, there is one built as a Custom Web Control.
Two symptoms worth watching: alarms that have been active for more than 24 hours, and alarms that repeat three or more times in one minute Chemical Engineering. Neither is asking for an action: both are asking for someone to redesign them.
UX on the shop floor: fingers, hurry and distance
What digital product design has known for thirty years, applied to a panel
An HMI is software, and software obeys the same usability laws as any app. Jakob Nielsen's ten heuristics have not changed since 1994 NN/g; these four prevent the most mistakes on the plant floor.
- 01
Visibility of system status
Every command gets an immediate response, and the screen separates what was requested from what happened: “open” is not “opened.”
- 02
Error prevention
Preventing the error beats warning afterwards. Critical actions ask for confirmation; impossible ones are not offered at all.
- 03
Recognition rather than recall
Ranges, units and setpoints in plain sight. Anything the operator has to memorize will eventually fail on a night shift.
- 04
Consistency and standards
The same symbol, the same color and the same place on every screen. Surprise is the enemy of speed.
Three time limits that do not depend on technology
0.1 s
The system feels instantaneous. This is your budget for confirming a tap.
1 s
The flow of thought is not broken, although the delay is noticed.
10 s
The limit of attention. Beyond it, show progress.
Those limits are not new either: Nielsen published them in 1993 NN/g. On a panel they mean every tap needs a visible reaction within a tenth of a second, even if the PLC takes longer to confirm the command.
And then there is the finger. Fitts's law says a target is hit faster the bigger and closer it is NN/g, and WCAG 2.2 puts numbers on it: 24 × 24 px as the minimum and 44 × 44 px as the enhanced criterion W3C. On a panel operated standing up, in a hurry or with gloves on, the web minimum falls short: aim for the enhanced size and keep apart the buttons that must not be pressed by mistake. There are input controls designed for exactly that.
Actual size on your screen
Tap both and feel the difference
24 px · minimum
Hits: 0
44 px · enhanced
Hits: 0
Where native objects fall short: Custom Web Controls
What is missing from the toolbox can be built with web technology
Go back over what the previous chapters ask for: analog indicators with their normal range, embedded trends, Level 1 dashboards, alarms with a shape and a number. With the standard objects of a SCADA system you can get part of the way, at the cost of stacking rectangles, scripts and engineering hours.
A Custom Web Control (CWC) is the way out: a control built with HTML, CSS and JavaScript that WinCC Unified and WinCC V8 treat as just another object. You place it on the screen from TIA Portal (WinCC Unified) or from Graphics Designer (WinCC V8); it exposes properties you bind to tags and events that trigger actions. Inside, it can be anything a browser can do.
What a CWC solves in a single part
Advanced visualization
Sankey, radar, Gantt, heat maps or complete dashboards.
Data with context
Indicators with zones, limits and a trend in the same control.
Modern interaction
Navigation menus, filterable tables, date pickers or recipe managers.
Maintained in one place
Configured once, reused on every screen and updated in a single spot.
From the HMIx catalog
Three Custom Web Controls from the catalog
If you want to understand how one is built on the inside, the Custom Web Controls guide makes one step by step. If you just want to use them, there are 232 free Custom Web Controls waiting in the catalog.
Browse the free Custom Web ControlsA symbol that tells its own state: dynamic SVGs
Any piece of equipment, with all its states, in a single file
For equipment, the toolkit part is the dynamic SVG: a vector graphic (.svghmi) with its own parameters. You bind those parameters to tags and the symbol changes color, shows or hides parts, raises a level or spins an impeller, with no scripts on the screen.
The saving is in the arithmetic. A pump with four states drawn with standard objects means four groups of shapes with their animations, repeated in every instance. With a dynamic SVG it is one file and a handful of parameters, whether you have eight pumps or two hundred.
One file, eight pumps, every state
Symbol parameters
- Running
- Bool
- true
- Fault
- Bool
- false
- Speed
- Real
- 70
The same file, eight instances
Being vector, it stays sharp on a 7-inch panel and on the control-room video wall. And being a file, the day the style guide changes you replace it once.
Realistic or schematic? It depends on the level. Restrained symbols work better on overviews; on an equipment detail screen or a machine panel, a faithful drawing helps people recognize what they are looking at. The catalog has both kinds.
From the HMIx catalog
Five dynamic SVGs from the catalog
The dynamic SVG guide explains the format from scratch. And if you would rather start from the result, there are 417 free dynamic SVGs, with curated picks of valves, pumps and motors.
Browse the free dynamic SVGsDoesn't exist yet? Describe it
From text to control, ready for WinCC, without writing code
No catalog has exactly your machine. That is what the HMIx AI generator is for: you describe the control or the symbol in your own words and get a Custom Web Control or a dynamic SVG with its properties defined, a simulation to try it out and the package ready to import.
You don't need to know HTML or SVG, and you can start for free on the Community plan. If you want the result to fit in, upload a screenshot of your screens and the generator will match the design to your style.
This is how you ask for a control
You
Horizontal temperature indicator with a normal range between 140 and 170 °C, high and high-high alarm limits, and the trend of the last few minutes.
HMIx generator
First version ready. Properties: Value, NormalMin, NormalMax, High and HighHigh. Try it in the simulation and tell me what to change.
Preview
163°C
- 01
Describe
What it should show and what data it receives. You can attach a reference image.
- 02
Refine
Correct it by chat or with the visual editor and test it in the simulation.
- 03
Integrate
Download the package and import it into TIA Portal (WinCC Unified) or WinCC V8.
Free on the Community plan · no prior knowledge needed
Before you ship: twelve checks
The whole guide, in a list you can take with you
Tick what your screen already does. Whatever stays unticked is your to-do list.
0 of 12
Missing parts to get there? The catalog has 654 free resources for WinCC Unified and WinCC V8, and whatever is not there you can generate with AI.
Frequently asked questions
What is ISA-101?
ANSI/ISA-101.01-2015 is the International Society of Automation standard for designing, implementing and maintaining human-machine interfaces (HMIs) in process automation systems. It defines a lifecycle, a four-level display hierarchy and the system documents: philosophy, style guide and toolkit. It does not prescribe specific colors or symbols.
What is a high-performance HMI?
It is a design approach focused on helping the operator detect and resolve abnormal situations early: neutral backgrounds, color reserved for the abnormal, analog indicators with their normal range, embedded trends and a clear display hierarchy. The term was popularized by the book The High Performance HMI Handbook.
Which colors should a SCADA screen use?
A neutral background, equipment and piping in muted tones, and saturated colors only for alarms and abnormal states, always paired with a shape or text. Alarm colors should not be used for anything else.
How many alarms are too many?
The reference guides (EEMUA 191 and ISA-18.2) set the target at around one alarm every 10 minutes per operator in normal operation, and the manageable maximum at about 12 per hour. More than 10 new alarms in 10 minutes is considered an alarm flood.
What is the difference between a Custom Web Control and a dynamic SVG?
A dynamic SVG is a vector symbol with parameters that change its appearance: ideal for equipment, valves or instruments. A Custom Web Control is a small web application with properties, events and methods: ideal for advanced charts, tables, menus or dashboards. They complement each other.
Are HMIx resources free, and do they work with TIA Portal?
The resources mentioned in this guide are published as free; all you need to download them is an HMIx account. Custom Web Controls and dynamic SVGs are used in WinCC Unified, which is engineered from TIA Portal, and in WinCC V8. Each product page states its compatibility.
Sources
Every figure in this guide comes from these publications. ISA standards are paid documents, so we link their official pages and publicly available analyses.
- HSE (UK), “Better alarm handling”, Chemicals Sheet No 6
- Errington, DeMaere & Wade (2005), “Supporting Key Console Operator Interactions through the Control System Interface”, NOVA Chemicals / ASM Consortium
- ISA, ISA-101 series: Human Machine Interfaces for Process Automation Systems
- ISA, ISA-18 series: Management of Alarm Systems for the Process Industries
- Control Global (2017), “Advice on implementing ANSI/ISA standards for operator interfaces”
- Control Global (2011), “The ultimate HMI”
- Chemical Engineering (2016), “Alarm Management By the Numbers”
- Nielsen Norman Group, “10 Usability Heuristics for User Interface Design”
- Nielsen Norman Group, “Response Times: The 3 Important Limits”
- Nielsen Norman Group, “Fitts's Law and Its Applications in UX”
- W3C, WCAG 2.2 — Understanding SC 1.4.1 Use of Color
- W3C, WCAG 2.2 — Understanding SC 1.4.3 Contrast (Minimum) and SC 1.4.11 Non-text Contrast
- W3C, WCAG 2.2 — Understanding SC 2.5.8 Target Size (Minimum)
- National Eye Institute (NIH), “Color Blindness”
- Siemens, Programming Custom Web Controls (RT Unified)
- Siemens, Managing dynamic SVG graphics (RT Unified)
- HMI design
- SCADA design
- ISA-101
- High-performance HMI
- Industrial UI/UX
- Alarm management
- ISA-18.2
- WinCC Unified
- WinCC V8
- TIA Portal
- Custom Web Control
- Dynamic SVG